Troubleshooting#
Problem | Indication | Solution |
---|---|---|
The device does not operate | The status LED is off | • Check power to the MIVO Connect system. • Ensure the expansion cable connectors are fully inserted. |
The device does not operate | The status LED is solid red | Contact support. |
No response from meter | The MBUS Status LED flashes red every 2 seconds | The product does not detect any M-Bus loads. Check the installation for any open circuits. |
No response from meter | The MBUS Status LED is solid red | The device has detected an overload or a possible short circuit in the system. Check the installation. |
No response from meter | The MBUS Status LED is quickly flashing red | The device detects a short circuit. Check the installation. |