Installation
Mounting#
The MIVO Connect is designed for indoor use and must be mounted in an electrical enclosure with a suitable IP rating and supported on a DIN-Rail. The enclosure must cover the power terminals and the expansion connector.
The product must be mounted vertically with terminal connectors 1 and 2 (see the Product Description) facing upwards; no other rotation is allowed. Always allow adequate ventilation clearances—40 mm above and 20 mm below the device—to prevent overheating. Keep other heat-generating devices at least 10 mm away from this product.
Mounting
- Tilt the product up and place the topmost latches on top of the DIN-Rail.
- Tilt the product down until the bottom latch snaps into place. If necessary, use a small screwdriver to pull the latch (item 16 in the Product Description) down.
Removal
Ensure power is disconnected before proceeding.
- Disconnect all cables.
- Pull the bottom latch (item 16 in the Product Description) down with a screwdriver and tilt the product upwards.
- Lift the device up and then move the product straight out.
Connections#
MIVO Connect#
Connection
- Make sure the power to the system is disconnected.
- Connect the wider of the two cable connectors to the connector labeled “Expansion In” on the Extender and push firmly until the latch engages with a click.
- Connect the other end of the cable to the previous Expansion or Expansion Out port in the same way.
- Repeat the process for all Extenders.
Disconnection
- Make sure the power to the system is disconnected.
- Hold down the connector latch and pull the connector straight out.
M-bus#
Connection of M-Bus Cables
- Peel 8 mm of insulation from the cables to be connected.
- Push down the orange button of the terminal to which you want to connect the wire and keep it pressed while inserting the cable at a 45° angle.
- Once the cable is inserted, release the button and proceed with the next terminal.
Disconnection of M-Bus Cables
- Push down the orange button and hold it while pulling the cable out.